HomeMy WebLinkAbout18156 018770 051 07-25-2024 LDLTTEST AEPACS LINE AND LEAK DETECTOR TEST Digitally signed by:
Automatic Line Leak Detector (ALLD) AEPACS
Date:2024.12.06 05:22:02-06:00
Reason:Submission Data
and/or Line Tightness Test Report Location:State of Alabama
version 3.5
(Submission#: HQ8-NWXM-GQGBA,version 1)
Details
Submission Alias Automatic Line Leak Detector(ALLD)and Line Tightness Test Report(Form 566)
Submission ID H08-NWXM-GQGBA
Form Input
Report Entry
Submission Method for Test Results
Upload PDF Copyof ADEM Automatic Line Leak Detector(ALLD)and Line Tightness Test Report(Form 566)
Is the submission in response to an Warning Letter I Notice of Violation I Notice of Proposed Delivery Prohibition?
No
Site Information
Site Name
CIRCLE K#2709068
Permit Number(Facility ID Number)
23413-051-018770
Site Address
1167 HWY 14
MILLBROOK,AL 36054
United States
Upload Test Results
Type of Test Performed
Automatic Line Leak Detector(ALLD)
Line Tightness Test
Please select®Did Not Test®as the test result and provide the reason for not testing for all situations in which the specific
equipment was not tested or not required to be tested.
Automatic Line Leak Detector(ALLD)Test Results
Tank Install Data Tank Product Tank Status Test Data Test Result
12/22/2022 54282 Unleaded gasoline Currently in Use 0725/2024 Pass
1222/2022 54283 Premium gasoline,Etharol free gasoline Currently in Use 07252024 Pass
1222/2022 54284 On road diesel,Otter Currently in Use 07252024 Pass
1222/2022 54284 On road diesel,DEF Currently in Use 07252024 Pass
Line Tightness Test Results
12/6/2024 5:22:02 AM Page 1 of 2
Tank Install Date Tank Product Tank Status Test Date Test Result
NONEPROVIDED 54282 Unleaded gasoline Currently in Use 0725/2024 Pass
NONEPROVIDED 54283 Premium gasoline,Ethanol free gasoline Cuneraly in Use 07252024 Pass
NONEPROVIDED 54284 On road diesel,Other Cuneraly in Use 07252024 Pass
Attach the PDF file of the test form
9068-LINE-LD 07252024.pdf-12/06/2024 05:18 AM
Comment
NONEPROVIDED
12/6/2024 5:22:02 AM Page 2 of 2
LINETT
ADEM SEl-9264623
LINE TIGHTNESS TEST REPORT
Questiore on hi compete this form should be directed to the Groundwater Branch UST Com lien Unit at 3341 270-561
Facifirry Name_ Circle K#2709068 Owner: Circle K
Address: 1167AI-Hwyl4 Address. Environmental Shared Services Gulf Coast 1100 Si s
City,County, Zip: Millbrook ELMORE 360541 City Stat9,06,11II&IIIII NC 27606
Facility I.D.#: 23413-051-018770 1 Phone# 850-316-6673
Tester Name_ Andrew Parnell I Tester Phone# 800-964-1250
Tester Certificaton_ Certficaton Expiration
Tester Company_ Tanknology,Inc.
Instructions
1. Complete this farm,include all the test data,and submit to: Groundwater Branch,PO Box 3C1463 Montgomery,AL 36130-1463,or
facto (334)27C-5631,or email to. USTccmolance(a)adem alabamaaev. Test data must include waiting time between delivery
and testing,start time,eM time,recorded volume changes and limes,correction factors and calculations,and calculated
leak rate for every test performed or the submittal will not be acceofed.
2. This farm allows you to record up to 6 ADEM Unique Tank Numbers,assuming that the Faulity ID Number and the test equipment
remain the same_
3. The tightness test equipment used must be approved by ADEM. Visit the Ni w4bsile at wwwmwolde.ora to view a list of
releaselleak selection equipm unilmethms that ADEM approves for use In Aabama_
4. Testing must be performed in ad romance with the manufacturers instructions_
5. Keep a recent copy or this testing for 3 years.
Reason far Test-circle all that apply 0 (Annual Test)El (New Installation) (Required by ADEM) C(Re spouse to SIR Problem)
Manufacturer of Test Equipment, Tanknology Model or Version. TLD-1
ADEM Unique Tank Tl 72 T3 T4
Product stored REGULAR PREMIUM ETHANOL Diesel
fiberglass 66fiberglass 01berglass berglass benglass Ltiberglws
Piping material tested ❑flexible ❑flexible ❑lemnic ❑nexlble ❑flexible [flexible
Lsteel Osteel Osteel Osteel Ostend Lsteel
Piping capacity 200 200 200 200
allons
Line pressure during test 60 60 60 60
s
Equipment threshold 0.05 0.05 0.05 0.05
h
Measured leak rate 0 0 0 0
h
pass _pass s I _pass
Results oftest: Dial Fur itt it l Mail
Utnwnclusive Lini sive ❑nconclusive L msonGusive eincundwree Linconclusive
Testers initials and AP 7/25/20 P 7/25I20 P 7/25/20 AP 7/25/20
date tested
Repairs Needed Date of Repair Description of any Repairs
Certification
1 century under penalty of law that the lest was performed in accordance with al€regulatory requirements of ADEM administrative cote
rule 335-6-15 and that the submitted information is true, accurate,and complete.
Signamre of Tesler 0a1e: 0 712 5/2 0 2 4
ADEM Farm 477 mt l/10 m2(revised 3/1a)
LDLTTEST
r
AoeM
AUTOMATIC LINE LEAK DETECTOR (ALLD) and LINE TIGHTNESS TEST REPORT
c Fa c lily Name_ Circle K#2709068 Owner: Circle K
AUUI e5S 1167 AL H 14 Address: Environmental Shared Services Gulf Coast 1100
City,-County, Zip: Millbrook ELMORE 36054 City, State$i01s Suite 100 NC 27606
Facility I .#: 23413-051-018770 Phone#: 850-316-6673
Tester Name.- Andrew Parnell Tester Phone if 800-800-4633
Tester Certification_ 182137 Certification Expiration 06/05/2025 f
Tester Company: Tanknology.Inc. Test Date: 07/25/2024
Instructions
1. Sulxnitihisform,attach all testdam far every test peolomled,and subma a eompletetl copy of this Conn to' Gledhil tel Branch,Po
Bmx3m1463, Montgomery,AL361M-1463,orfaxtm: (334)2705631,memallie: USTcompliance(uladernerahamagov This Pone
must W mmpleted and induded mM the test data or the submhtal vnll nM be accepted.
2. This fart,allows up to 6 ADEM Unique Tank Numbers assuming that the Facility ID Number and test equipment remain the same.
3. Testing must be performed in accordance with a nationally recognized code of practice(such as PEI RP-1200 or equivalent)or the
manufacturers instructions.
4. Line tightness test equipment used must he approved by ADEM. V sit(he"GME vrehsae alwww m Me org to view a list a
raleaselleak detection eq,upmenVnlethods that ADEM approves for use in Al
5. Automatic Line Leak Detectors are designed to he tested in-place Da not remove and lest outside mike tank system.
6 Keep a copy of mis Testing far 3 years ouestiom on haw to complete this form should be,diweted to the Groundwater Branch.UST
Compliance Unit at(334)270-51l
Type of Test Performed-check all that apply iQlAutmmahc Line Leak Detector(ALLD) ❑Line Tightness Test
Reason for Test-check all that apply aAnnual Test ❑New Installation CRequired by ADEM Enforcement Action
Manufacturer of ALLD Test Equipment: TANKNLOGY Ml or Version:FTA
Manufacturer of Line Tightness Test Equipment Made;or Version[
ADEM tlni ue Tank a T1 T2 T3 T4
Product Stored REGULAR PREMIUM ETHANOL Diesel
fiberglass Ofiffergess 011berplass kolfiberglass berglass Lifflienglass
Piping material Efienble Dmekible Ed le Eloamble Dllexible Eldelune
Esteet Dsteel Elsteel Meet E'eteel ❑steel
Apprax_length of piping 200 200 200 200
run tested nearest foot
Piping capaciry 32 32 32 32
(gallons)
Automatic Line Leak Detector Test
Type ei ALLD AElm2ronic
mechanical mechanical mechanical mechanical Jmechanical
Deleatione: Delectronic Delectionic Delectronk Eeleetronic
Line pressure 10 10 10
durin ALLD test siMeasured ALLD leak rate 3.0 3.0 3.0
Results of ALLD test ss it ssails it ss it ss ail
nwnclusive ncanclusive ncsnclusire nconclusive Jnconclusim
Line Tightness Test
Line pressure
coming line test si
Measured line leak race
Results of line Epass Cfail Dpass 0fail C6ass Dfail Kass Dail Ds 7 mastail Li Dfail
tightn m stest Linconchch. ❑inrna lusive Linconclusive Limoonclusive ,conclusive Einconcluslve
Repairs Needed Date of Repair Description of any Repairs
Tester's Signature:
ADEM Farm 566