HomeMy WebLinkAbout18370 000062 101 11-21-2019 LDLTTEST QMV LINE AND LEAK DETECTOR TEST 62585.21 ()000(P2 — L D L-T -TCST
LINETT
ADEM .. ..
LINE TIGHTNESS TEST REPORT
puesticns on howl.complete this form should be directed to the Groundwater Branch,UST Compliance Unit at 334 29m-5665
Facilit Name: One Stop 72- Liberty Store Owner.
Address: 1175 W South BIVO Address:
City, County,Zip: Montgomery,AL Citir. State Zip:
Facility I.D. I Phone#: .
Tester Name:If RA.. HA ii. ''" '>>* - 11 Tester Phone*
Tester Certification: FI-578188 I Certification Expiration: 10-22-21
Tester Com arr :Clemens Fuel Systems, n .
Instructions
1. Complete this form,include ail are test data,and submit to: Groundwater Branch,PO Box 301463 Montgomery,AL 36130.1463, or
fax to: (334)270-5631,or email to: USTmmolance(, ademalabama.gov. Test data must include waiting time between delivery
and testing,start time,end time,recorded volume changes and times,correction factors and calculations,and calculated
leak rate for every test performed or the submittal will not be accented.
2. This form allows you to record up to 6 ADEM Unique Tank Numbers,assuming that the Facility In Number and the test equipment
remain the same.
3. The tightness test equipment used must be approved by ADEM. Visit the NWGIDE website at www.nwglde.org to view a list of
releass/leak detection equomenUmethods that ADEM approves for use in Alabama. -
4. Testing must be performed In accordance with the manufacturer's instructions.
S. Keep a record copy of this testing for 3 years.
Reason for Test-circle all that applg nnual Testf-111ew Installation quired by ADEM Response to SIR Problem)
Manufacturerofrest Equipment: EStabrooks - Model or version: Ezy line tester
ADEM Unique Tank#
Product stored PE 1 PE2 Premium Premium 2 Regular Diesel
®fiberglass ®fiberglass ®fiberglass ®fiberglass ®fiberglass ®fiberglass
Piping material tested Ofleldble Oflexible Dflexible Dilatable Ora le Oflexible
Osteel Dsteel Ostael Osteel Osteel Osteel
Piping capacity
(gallons) 10 G 1013 1013 10 G 10113 1013
Dne pressure during test 50 psi 50 psi 50 psi 50 psi 50 psi 50 psi
(psi)
Equipment thresholdsho6 -.05 -.OS -.05 -.05 -.05 -.05
h
Measured leak rate-(oph) D O O O O 0
®pass ®pass ®Pass ®pass - ®pass ®pass
Results of test: Ofail Ofall OfaiI Ofail E3 Ofail
Dinconclusive Clud.,mclusive Oinconclusive Oinconclusive Oinconclusive Oinconciusive
Tester's initials and DH 11-21-19 D 11-21.1 DH 11-21-19
date tested DH 11-21-19 DH 11-21-19 DH 11-21-19
Repairs Needed Date of Repa Description of any Repairs
Certification
I certify under penalty of law that the test was performed In accordance with all regulatory requirements of ADEM administrative code
rule 335-6-15 and that the submitted infornaton is true,accurate,and complete.
Signature of Tester: ` - Date: 11-21-19
ADEM Form 477 ml 1110 m2(revised 3118)
ADEM
AUTOMATIC LINE LEAK.DETECTOR(ALLD) TEST.REPORT
Questions on how to cdm fete this form should be directed to the Groundwater Branch,UST Compliance Unit at 334)270S555
FaciQ Name: One Stop 72- Liberty Store Owner:
Address: 1175 W South Blvd Address:
City, County,Zip: Montgomery City,State,Zip:
Facili LD.#: Phone#:
Tester Name: MllasRirdii 1 Tester Phoria#: 850-265-8881
Tester Certification: FL-578186 - Certification Expiration: 1 U-22-21
Tester Com an
Instructions
1. Submit this form,attach all test data for every test performed,and submit a completed copy of this form to: Groundwater Branch,PO
Box 301463 Montgomery,AL 36130-1463.or fax to: (334)270.5531,or email to: USTcomphance'Madem.alabama.cov. Thisform
must be completed and included with the test data or the submittal will not be accepted.
2. This forth allows you to record up to 6 ADEM Unique Tank Numbers,assuming that the Facility ID Number and the test equipment
remain the same.
3. Testing must be performed In accordance with a nationally recognized code of practice(such as PEI RP-1200 or equivalent)or the
manufacturer's Instructions.
4. Automatic Line Leak Detectors are designed to be tested in-place. Do not remove and test outside the tank system.
5. Keep a record copy of this testing for a years.
Test Method Used-circle: PEI RP-1200) 1^anufacturer) (ther(specify)
Reason for Test-drele all that apply: IMnual Test) I New Installation)IV Required by ADEM)
Manufaclurerof Test Equipment Estabrooks - Model orversion: EZY-3 leak dector
ADEM Unique Tank# - -
Product Stored Pet Pe2 Premium -Premium 2 Regular Diesel
®fiberglass ®fiberglass ®fiberglass 18fberglass ®fi erglass ®fiberglass
Piping material tested Ofiemble flexible Dfiexible Oflexible Ofiexible Oflexible
Dsted Dsteel Dsteal Osteel [lateral Defeat
Approximate length of
piping run tested 200 Ft 200 Ft - 200 Ft 200 ft 200 ft 200 ft
nearest foot
Type of ALLD ®mechanical IHmechanical ®mechanical ®mechanical ®mechanical ®mechanlcal
Delectronic Oelectronic Delectronic Delectronic Delectronic Delectronic
Line pressure 25 psi 25 psi 25 SI 25 Si 25 psi 25 psi
Burin test i
Measured leak rate(gph) 3 gph 3 gph 3 gigh 3 gigh 3 gph 3 gph
®pass - ®pass ®pass ®pass ®Pass ®pass
Results of test Ofall Ofall ofail ofail Ofall Ofall
Dinconclusive Oinecenclusive Olrrconclusive I Dinconctusive Dinconclusive Oinconclusive
Tester's initials and date tested DH 11-21-19 DH 11-21-19 DH 11-21-19 DH 11-21-19 DH 11-21-19 DH 11-21-19
Repairs Needed Date of Repair Description of any Repairs
Certification
I certify under penalty of law that the test was performed in accordance with all regulatory requirements of ADEM administrative;code
rule 335-6-15 and that the submitted information is true,accurate,and complete.
SlgreWre of Tester — Date: 11-21-19
ADEM Form 551 ml 1110 m2(revised 3118)